Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual
Page 106

5-47 Specifications
Publication 198-UM002A-EN-P December 2001
Table 5.29 198-IB2XOB1 Specifications
Terminal Block (5.08 mm Pitch 4-Position)
Connection Capacity
Solid wire
0.13…1.5 mm
2
(24…16 AWG)
Flexible wires
0.13…2.5 mm
2
(24…14 AWG)
Flexible wires with ferrules
0.5…2.5 mm
2
(20…14 AWG)
Plastic collar
1.5 mm
2
(16 AWG)
Wire Type
Use 75 C copper wire min.
Tightening Torque
Spring clamp
Terminal Block (5.08 mm Pitch 2-Position)
Connection Capacity — Flexible wire
0.13…1.5 mm
2
(24…16 AWG)
Wire Type
Use 75 C copper wire min.
Tightening Torque
Insulation displacement
Electrical
Module Operating Voltage Range
11…25V DC
Module Voltage Rating
24V DC
Module Current Draw
14 mA @ 24V DC
Input Voltage Rating
24V DC
Input On-State Voltage Range
10…24V DC
Input On-State Current
3.0 mA @ 10V DC
7.2 mA @ 26V DC
Input Off-State Voltage Range
0…5V DC
Input Off-State Current
<1.5 mA
Input Filter — Software
Selectable (with two I/O modules)
Off to On
1, 2, 4, 8, 16 ms
On to Off
1.3, 2, 4, 8, 16 ms
Input Compatibility
IEC 1+
Output Voltage Rating
24V DC
Output Load Current
2 A per output
Switching Device
Solid-State — N300, DC14
Module Isolation
132V AC working voltage
1500V AC for 1 s