Chapter Objectives

This chapter contains information about:

Device storage and operating environment

Mounting

Connecting and wiring

Storage and Operation

To prolong the product life, take the following precautions:

Store within an ambient temperature range of –40…+85

°

C (–40…+185

°

F).

Store within a relative humidity range of 0…95%, non-condensing.

Avoid storing or operating the device where it could be exposed to a corrosive
atmosphere.

Protect from moisture and direct sunlight.

Operate at an ambient temperature range of –25…+60

°

C (–4…+140

°

F). The

Modular DSA I/O System enclosure is suitable for an ambient of –25…+40

°

C.

Modular DSA I/O System is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use in a clean,
dry environment (Pollution Degree 2

)

.

Pollution Degree 2 is an environmentally where, normally, only non-conductive pollution occurs except

occasionally a temporary conductivity caused by condensation shall be expected.

Pollution Degree 2 is an International Electrotechnical Commission (IEC) designations.