Discrete output point object – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 163

Advertising
background image

DeviceNet Information A-29

Publication 198-UM002A-EN-P December 2001

Multiple instances of the Discrete Input Point Object are supported. All instances contain the
following attributes.

The following common services are implemented for the Discrete Input Point Object.

Discrete Output Point Object

CLASS CODE 0x0009
The following class attributes are supported for the Discrete Output Point Object:

Multiple instances of the Discrete Output Point Object will be supported. All instances will
contain the following attributes.

The following common services will be implemented for the Discrete Output Point Object.

Table A.51

Attribute ID

Access Rule

Name

Data Type

Value

3

Get

Value

BOOL

0=OFF, 1=ON

Table A.52

Service Code

Implemented for:

Service

Class

Instance

Name

0x0E

Yes

Yes

Get_Attribute_Single

0X10

No

Yes

Set_Attribute_Single

Table A.53

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

1

2

Get

Max Instance

UINT

0…80

Table A.54

Attribute ID

Access Rule Name

Data Type

Value

3

Get

Value

BOOL

0=OFF, 1=ON

5

Get/Set

Fault Action

BOOL

0=Fault Value attribute, 1=Hold Last State

6

Get/Set

Fault Value

BOOL

0=OFF, 1=ON

7

Get/Set

Idle Action

BOOL

0=Fault Value attribute, 1=Hold Last State

8

Get/Set

Idle Value

BOOL

0=OFF, 1=ON

Table A.55

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single