Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual
Page 91

Specifications 5-32
Publication 198-UM002A-EN-P December 2001
Figure 5.21 198-OW2-G4 Electrical and Application Schematic
Table 5.23 198-OW2-G4 Specifications
Connector (1/2 in. x 20 Female 4-Pin)
M12 Mounting Hole
16 mm (5/8 in.)
M12 Thread
1/2 in. x 20
M12 Connector Torque
1.4 Nm (12 lb-in.)
Electrical
Module Operating Voltage Range
11…25V DC
Module Voltage Rating
24V DC
Module Current Draw
50 mA @ 24V DC
Output Voltage Rating
120V AC
Output Load Current
4 A total (Out A + Out B)
Switching Device
Relay — B300, AC15, DC13
Module Isolation
132V AC working voltage
1500V AC for 1 s
3
4
1
120V AC
(24V DC)
PE
PE
PE
PE
Ou
t B
Ou
t A
L (+V )
N(0V)
2
2
1
4
3
MALE
3
2
1
3
2
1
FEMALE
3
2
1
3
2
1
MALE
MALE
DI N V alve
T-Connector
3
4
1
120V AC
(24V DC)
PE
PE
PE
PE
Ou
t
B
Ou
t
A
L ( +V )
N ( 0V )
2
2
1
3
2
1
3
DI N V alve
Typical Installation and Wiring
Typical Wiring for Relay Valve Module 198-OW2-G4 to Two DIN Valves