Specifications 5-32

Publication 198-UM002A-EN-P December 2001

Figure 5.21 198-OW2-G4 Electrical and Application Schematic

Table 5.23 198-OW2-G4 Specifications

Connector (1/2 in. x 20 Female 4-Pin)

M12 Mounting Hole

16 mm (5/8 in.)

M12 Thread

1/2 in. x 20

M12 Connector Torque

1.4 Nm (12 lb-in.)

Electrical

Module Operating Voltage Range

11…25V DC

Module Voltage Rating

24V DC

Module Current Draw

50 mA @ 24V DC

Output Voltage Rating

120V AC

Output Load Current

4 A total (Out A + Out B)

Switching Device

Relay — B300, AC15, DC13

Module Isolation

132V AC working voltage
1500V AC for 1 s

3

4

1

120V AC
(24V DC)

PE
PE

PE
PE

Ou

t B

Ou

t A

L (+V )

N(0V)

2

2

1

4

3

MALE

3

2

1

3

2

1

FEMALE

3

2

1

3

2

1

MALE

MALE

DI N V alve

T-Connector

3

4

1

120V AC
(24V DC)

PE
PE

PE
PE

Ou

t

B

Ou

t

A

L ( +V )

N ( 0V )

2

2

1

3

2

1

3

DI N V alve

Typical Installation and Wiring

Typical Wiring for Relay Valve Module 198-OW2-G4 to Two DIN Valves