A-30 DeviceNet Information

Publication 198-UM002A-EN-P December 2001

Discrete Input Group Object

CLASS CODE 0x001D
No class attributes are supported for the Discrete Input Group Object.
A single instance of the Discrete Input Group Object is supported. It contains the following
attributes.

The following common services will be implemented for the Discrete Input Group Object.

Discrete Output Group Object

CLASS CODE 0x001E
No class attributes are supported for the Discrete Output Group Object.

A single instance of the Discrete Output Group Object is supported. It contains the
following attributes.

The following common services will be implemented for the Discrete Input Group Object.

Table A.56

Attribute ID

Access Rule

Name

Data Type

Value

3

Get

Number of Instances

USINT

1…64

4

Get

Binding

Array of UINT

List of DIP instances

6

Get/Set

Off_On_Delay

UINT

0

µ

s; 2000

µ

s; 4000

µ

s,

8000

µ

s; 16000

µ

s

7

Get/Set

On_Off_Delay

UINT

0

µ

s; 2000

µ

s; 4000

µ

s,

8000

µ

s; 16000

µ

s

Table A.57

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Table A.58

Attribute ID

Access Rule

Name

Data Type

Value

3

Get

Number of Instances

USINT

0…80

Table A.59

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single