Acknowledge handler object, Devicenet interface object – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 165

Advertising
background image

DeviceNet Information A-31

Publication 198-UM002A-EN-P December 2001

Acknowledge Handler Object

CLASS CODE 0x002b
No class attributes will be supported for the Acknowledge Handler Object.
A single instance (instance 1) of the Acknowledge Handler Object will be supported. The
following instance attributes will be supported.

The following common services will be implemented for the Acknowledge Handler Object.

DeviceNet Interface Object

CLASS CODE 0x00B4
This “vendor-specific” object includes no class attributes.
A single instance (instance 1) of the DeviceNet Interface Object is supported:

Table A.60

Attribute ID

Access Rule Name

Data Type

Value

1

Get/Set

Acknowledge Timer

UINT

milliseconds

2

Get

Retry Limit

USINT

1

3

Get

COS Producing Connection Instance UINT

4

Table A.61

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Table A.62

Attribute
ID

Access
Rule

Name

Data Type Min/Max

Default

Description

7

Get/Set Prod Assy Word 0 USINT

0…51
0…60

1

Defines Word 0 of Assy 120

8

Get/Set Prod Assy Word 1 USINT

0…51
0…60

2

Defines Word 1 of Assy 120

9

Get/Set Prod Assy Word 2 USINT

0…51
0…60

3

Defines Word 2 of Assy 120

10

Get/Set Prod Assy Word 3 USINT

0…51
0…60

4

Defines Word 3 of Assy 120

13

Get/Set COS Mask

WORD

0…FFFF

0xffff

1=Module COS enabled
0=Module COS disabled

16

Get/Set Consumed Assy

USINT

0…187

104
106

Assembly instance number that
defines the consumed I/O data
format.

17

Get/Set Produced Assy

USINT

100…190

105
107

Assembly instance number that
defines the produced I/O data
format.

19

Get/Set Set To Defaults

BOOL

0…1

0

0=No action; 1=Reset

Advertising