Discrete input point object – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 162

Advertising
background image

A-28 DeviceNet Information

Publication 198-UM002A-EN-P December 2001

Instances 5 and 6 are the available group 1 or group 3 explicit message connections that are
allocated through the UCMM. The following attributes are supported:

The following services are implemented for the Connection Object.

Discrete Input Point Object

CLASS CODE 0x0008

The following class attributes are supported for the Discrete Input Point Object:

Table A.48 Instances 5 and 6 Attributes

Attribute ID

Access Rule Name

Data Type

Value

1

Get

State

USINT

0=nonexistant
1=configuring
3=established
4=timed out

2

Get

Instance Type

USINT

0=Explicit Message

3

Get

Transport Class Trigger

USINT

0x83 - Server, Transport Class 3

4

Get

Produced Connection ID

UINT

Depends on message group and
Message ID

5

Get

Consumed Connection ID

UINT

Depends on message group and
Message ID

6

Get

Initial Comm Characteristics USINT

0x22

7

Get

Produced Connection Size

UINT

0x61

8

Get

Consumed Connection Size UINT

0x61

9

Get/Set

Expected Packet Rate

UINT

in milliseconds

12

Get

Watchdog Action

USINT

01 = auto delete
03 = deferred delete

13

Get

Produced Connection Path
Length

UINT

0

14

Get

Produced Connection Path

Empty

15

Get

Consumed Connection Path
Length

UINT

0

16

Get

Consumed Connection Path

Empty

Table A.49

Service Code

Implemented for:

Service Name

Class

Instance

0x05

No

Yes

Reset

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Table A.50

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

2

2

Get

Max Instance

UINT

0-64

Advertising