5-29 Specifications
Publication 198-UM002A-EN-P December 2001
Figure 5.19 198-OW2 Electrical and Application Schematic
Table 5.21 198-OW2 Specifications
Terminal Block
Connection Capacity
Solid wire
0.13…1.5 mm
2
(24…16 AWG)
Flexible wires
0.13…2.5 mm
2
(24…14 AWG)
Flexible wires with ferrules
0.5…2.5 mm
2
(20…14 AWG)
Plastic collar
1.5 mm
2
(16 AWG)
Wire Type
Use 75 C copper wire min.
Tightening Torque
Spring clamp
Electrical
Module Operating Voltage Range
11…25V DC
Module Voltage Rating
24V DC
Module Current Draw
50 mA @ 24V DC
Output Voltage Rating
120V AC
Output Load Current
5 A per output
Switching Device
Relay — B300, AC15
Module Isolation
132V AC working voltage
1500V AC for 1 s
198-OW2
L o r 24V
Ou t A
Ou t A
N or 0V
Ou t B
Ou t B
Load
Load
120V AC
or
24V DC
Typical Wiring