Specifications 5-18
Publication 198-UM002A-EN-P December 2001
Figure 5.11 198-IA2 Electrical and Application Schematic
Table 5.13 198-IA2 Specifications
Terminal Block (5.08 mm Pitch 4-Position)
Connection Capacity
Solid wire
0.13…1.5 mm
2
(24…16 AWG)
Flexible wires
0.13…2.5 mm
2
(24…14 AWG)
Flexible wires with ferrules
0.5…2.5 mm
2
(20…14 AWG)
Plastic collar
1.5 mm
2
(16 AWG)
Wire Type
Use 75 C copper wire min.
Tightening Torque
Spring clamp
Electrical
Module Operating Voltage Range
11…25V DC
Module Voltage Rating
24V DC
Module Current Draw
10 mA @ 24V DC
Input Voltage Rating
120V AC
Input On-State Voltage Range
79…132V AC
Input On-State Current
11 mA @ 79V AC
16 mA @ 120V AC
Input Off-State Voltage Range
<20V AC
Input Off-State Current
<3.5 mA
Module Isolation
132V AC working voltage
1500V AC for 1 s
Input Filter — Software
Selectable (with two I/O modules)
Off to On
1, 2, 4, 8, 16 ms
On to Off
1.3, 2, 4, 8, 16 ms
Input Compatibility
IEC 1+
198-IA2
L
IN 1
IN 2
N
N
N
Input contacts or solid state switch
Typical Wiring