Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 77

Advertising
background image

Specifications 5-18

Publication 198-UM002A-EN-P December 2001

Figure 5.11 198-IA2 Electrical and Application Schematic

Table 5.13 198-IA2 Specifications

Terminal Block (5.08 mm Pitch 4-Position)

Connection Capacity

Solid wire

0.13…1.5 mm

2

(24…16 AWG)

Flexible wires

0.13…2.5 mm

2

(24…14 AWG)

Flexible wires with ferrules

0.5…2.5 mm

2

(20…14 AWG)

Plastic collar

1.5 mm

2

(16 AWG)

Wire Type

Use 75 C copper wire min.

Tightening Torque

Spring clamp

Electrical

Module Operating Voltage Range

11…25V DC

Module Voltage Rating

24V DC

Module Current Draw

10 mA @ 24V DC

Input Voltage Rating

120V AC

Input On-State Voltage Range

79…132V AC

Input On-State Current

11 mA @ 79V AC
16 mA @ 120V AC

Input Off-State Voltage Range

<20V AC

Input Off-State Current

<3.5 mA

Module Isolation

132V AC working voltage
1500V AC for 1 s

Input Filter — Software
Selectable (with two I/O modules)

Off to On

1, 2, 4, 8, 16 ms

On to Off

1.3, 2, 4, 8, 16 ms

Input Compatibility

IEC 1+

198-IA2

L

IN 1

IN 2

N

N

N

Input contacts or solid state switch

Typical Wiring

Advertising