Autobaud configuration, Autobaud configuration -7 – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 28

Advertising
background image

3-7 Operation

Publication 198-UM002A-EN-P December 2001

Autobaud Configuration

Automatic baud rate detection can be enabled/disabled by setting the value of the Autobaud
parameter (parameter 14).

1. To change the setting of the Autobaud parameter, click the pull down tab for that

parameter in the parameter window as shown below:

2. After choosing the desired setting, click the

$SSO\ button. You will then be asked to

download the configuration to the device. Click

<HV.

When the Autobaud parameter has the value Enable, the MDSA DeviceNet module will
attempt to match the network baud rate at power up. When the parameter has the value
Disabled, the powerup auto-baud feature is disabled. When the Autobaud parameter is
changed, the new value will be applied when the power is cycled after saving the value to the
device.

ATTENTION

!

Injury or damage may occur when parameters are not set according to
the application requirements

Advertising