Instance 189, Instance 190, Assembly object services – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual
Page 157

DeviceNet Information A-23
Publication 198-UM002A-EN-P December 2001
Instance 189
This is a “Read Only” status assembly.
Instance 190
This is a “Read Only” status assembly.
Assembly Object Services
The following services are implemented for the Assembly Object.
Table A.41 Instance 189 — DeviceNet Status
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
COS Idle
Poll Idle
COS Flt
Poll Flt
Exp Flt
COS Cnxn
Poll Cnxn
Exp Cnxn
1
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Minor
Fault
Network
Flt
Table A.42 Instance 190 — Module Status
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Status 8
Status 7
Status 6
Status 5
Status 4
Status 3
Status 2
Status 1
1
Status 16
Status 15
Status 14
Status 13
Status 12
Status 11
Status 10
Status 9
Table A.43
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single