Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 24

Advertising
background image

3-3 Operation

Publication 198-UM002A-EN-P December 2001

The user is now able to configure the MDSA. The following steps outline how to accept the
configuration of the I/O modules. This will result in the I/O Status LED changing from
solid red to off.

1. Double click on the MDSA icon. RSNetWorx will verify the identity of the device,

and then display the following screen:

2. Select the “Parameter” tab. RSNetWorx will prompt the user to upload the

parameters from the device. Select the

8SORDG button. The following screen appears:

3. From the screen shown, verify that the number of I/O modules and the names of the

modules recognized are correct. Select the Accept Config parameter (parameter 48 or
58). Double click the value of that parameter. A drop-down list of options will appear.
Select the Accept Config option.

4. Select the

$SSO\ button. RSNetWorx will ask you whether it should download the

changes to the device. Select

<HV. The device will reset, and the I/O Status LED will

turn off. The MOD/NET status LED will be flashing green, waiting to establish
connections to other nodes.