Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual
Page 116

5-57 Specifications
Publication 198-UM002A-EN-P December 2001
Assembly Instances 104 and 105 are default for 198-DNG. Assembly Instances 106 and 107
are default for 198-DN.
➊ When wired as shown in the following diagrams. Typical in a Distributed Starter. Input 1 represents the
disconnect status. Input 2 represents the fault status of the 160 drive.
Table 5.32 198-IB2XOB5S I/O Produced/Consumed Data
Input Data — Assembly Instance 103, 105, or 107
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
—
—
—
—
—
—
Input 2 ➊
Input 1 ➊
Input Data — Assembly Instance 101
Bit 3 or 7
Bit 2 or 6
Bit 1 or 5
Bit 0 or 4
—
—
Input 2 ➊
Input 1 ➊
Output Data — Assembly Instance 100, 102, 104, or 106
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
—
Speed 3
Speed 2
Speed 1
—
—
Run Reverse
Run Forward
Drive Control ➊
Run
Reverse
Run
Forward
Drive
Control
Run
Reverse
Run
Forward
Drive
Control
0
0
Stop
1
0
Run Reverse
0
1
Run Forward
1
1
Stop
Output Data Speed Settings ➊
Speed 3
Speed 2
Speed 1
Setting
Speed 3
Speed 2
Speed 1
Setting
0
0
0
Speed
Setting 1
1
0
0
Speed
Setting 5
0
0
1
Speed
Setting 2
1
0
1
Speed
Setting 6
0
1
0
Speed
Setting 3
1
1
0
Speed
Setting 7
0
1
1
Speed
Setting 4
1
1
1
Speed
Setting 8