Ow2-g4 series a (relay valve module), Ow2-g4 series a (relay valve module) -31 – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual
Page 90

5-31 Specifications
Publication 198-UM002A-EN-P December 2001
198-OW2-G4 Series A (Relay Valve Module)
Figure 5.20 198-OW2-G4 Series A Relay Valve Module
The Relay Valve module 198-OW2-G4 is designed to provide two output contacts to operate
up to two pneumatic valves. The power for the pneumatic valves is supplied separately via a
2-point insulation displacement connector.
Assembly Instances 104 and 105 are default for 198-DNG. Assembly Instances 106 and 107
are default for 198-DN.
Table 5.22 198-OW2S I/O Produced/Consumed Data
Input Data — Assembly Instance 103, 105, or 107
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
—
—
—
—
—
—
—
—
Input Data — Assembly Instance 101
Bit 3 or 7
Bit 2 or 6
Bit 1 or 5
Bit 0 or 4
Compressed format, no data sent
Output Data — Assembly Instance 102, 104, or 106
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
—
—
—
—
—
—
Output 2
Output 1
Output Data — Assembly Instance 100
Bit 3 or 7
Bit 2 or 6
Bit 1 or 5
Bit 0 or 4
—
—
Output 2
Output 1