Control supervisor object, Overload object – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 174

Advertising
background image

B-6 Motor Starter Operation

Publication 198-UM002A-EN-P December 2001

called out in the DeviceNet Motor Starter Profile as “Required” objects in all DeviceNet
Motor Starters. Their definitions are given below.

Control Supervisor Object

CLASS CODE 0x0029

This object only exists for units reporting a product type of 22 (Motor Starter). No class
attributes will be supported.
A single instance (instance 1) of the Control Supervisor Object will be supported. The
following instance attributes will be supported.

The following common services will be implemented for the Control Supervisor Object.

Overload Object

CLASS CODE 0x002c

No class attributes will be supported for the Overload Object.
No instance attributes will be supported for the Overload Object.
No common services will be implemented for the Overload Object.

Table B.8

Attribute ID Access Rule Name

Data Type

Value

1

Get/Set

Run 1

BOOL

Also maps to “Value” attribute of DOP 1

2

Get/Set

Run 2

BOOL

Also maps to “Value” attribute of DOP 2

3

Get

Running 1

BOOL

Also maps to “Value” attribute of DIP 1

4

Get

Running 2

BOOL

Also maps to “Value” attribute of DIP 3

Table B.9

Service Code Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Advertising