5-67 Specifications

Publication 198-UM002A-EN-P December 2001

198-G1P (Gland Plates)

Gland plates may also be referred to as cable plates. These plates are designed to cover
rectangular holes in standard enclosures and to allow easy power and signal access to the
enclosure.

Electrical

Module Operating Voltage Range

11…25V DC

Module Voltage Rating

24V DC

Module Current Draw

71 mA @ 24V DC

Input Voltage Rating

24V DC (sourced from module)

Input On-State Voltage Range

10…26V DC

Input On-State Current

3.0 mA @ 10V DC
7.2 mA @ 26V DC

Input Off-State Voltage Range

0…5V DC

Input Off-State Current

<1.5 mA

Input Filter — Software
Selectable (with two I/O modules)

Off to On

1, 2, 4, 8, 16 ms

On to Off

1.3, 2, 4, 8, 16 ms

Input Compatibility

IEC 1+

Output Voltage Rating

24V DC

Output Load Current

5 mA per output

Switching Device

Solid-State

Module Isolation

132V AC working Voltage
1500V AC for 1 min.

Environmental

Ambient Temperature

Operating

–25…+40

°

C (–4…+104

°

F)

Storage

–40…+85

°

C (–40…+185

°

F)

Relative Humidity

0…95% non-condensing

Shock

Operating

30 g peak acceleration

Non-Operating

50 g peak acceleration

Operating Vibration

10 g @ 58…2000 Hz
0.060 in. peak-to-peak displacement 2…57 Hz
Per IEC 68-2-6

Approvals

Agency Certification
(when product is marked)

cULus Listed
CE marked for all applicable directives

Table 5.35 198-IB2XOB2S-Q5 Specifications (Continued)