5-3 Specifications

Publication 198-UM002A-EN-P December 2001

I/O Status LED

The I/O status LED is a bi-colored (red/green) LED that provides status information on
communications between the I/O modules.

Table 5.2 I/O Status LED

For This State:

I/O Status LED

is:

To Indicate:

OFF

Off

No power or All outputs in the inactive state.
Configuration of I/O modules good.

I/O Idle

Flashing Green

The DeviceNet network has caused the outputs to be in
their idle state.
Idle/Program mode.

I/O Run

Green

Outputs are active.

I/O Recoverable Fault

Flashing Red

A connection controlling the outputs has timed-out.

I/O Unrecoverable Fault

Red

Configuration of I/O Modules does not match saved
configuration.
Power-up initialization of bus power failed.
CSUM Error at module X.
Invalid Module ID at module X.