A-32 DeviceNet Information

Publication 198-UM002A-EN-P December 2001

22

Get/Set I/O Module Status WORD

0…FFFF

0x0000

0=Data Valid at Module x
1=Data Invalid at Module x
Bit 0 = Module 1
Bit 15 = Module 16

23

Get

I/O Produced Size USINT

0…20

Size (in bytes) of I/O data
produced by poll, COS or Cyclic
connections.

24

Get

I/O Consumed
Size

USINT

0…16

Size (in bytes) of I/O data
Consumed by poll, COS or Cyclic
connections.

25

Get

I/O Error

USINT

0…14

0

0 = no error
1 = Module added
2 = Module removed
3 = Module different
4 = Invalid module ID
5 = Invalid module configuration
6 = Too many modules
7 = Csum error count > 500
8 = Unused
9 = EEPROM failure
10 = Unable to power bus
11 = Sensor or valve voltage
error
12 = Over-current
13 = Short term
over-temperature
14 = Long term over-temperature

26

Get

Error Location

WORD

0 = Module(x) OK
1 = Fault detected at module(x)
Bit 0 = Module 1
Bit 15 = Module 16

27

Get/Set Accept

Configuration

BOOL

0…1

0

0 -> 1 Save new I/O module
configuration to EEPROM

28

Get

CSum Count

UINT

CSum errors on the module bus.
Increases by 3 on error,
decrements by 1 on good bus
transaction.

29

Get

Module Error
Number

BYTE

0…16

Decimal number from 1…16
representing a module number.

30

Get

DeviceNet
Voltage

UINT

0…
65535 m
V

31

Get

Module Bus
Voltage

UINT

0…6553
5 mV

32

Get

I/O Bus Current

UINT

0…
19168 m
A

Coarse reading with 18 mA
resolution

33

Get

Number of
Modules

USINT

0…17

34

Get

Module ID Slot 1 USINT

0…17

35

Get

Module ID Slot 2 USINT

0…17

36

Get

Module ID Slot 3 USINT

0…17

37

Get

Module ID Slot 4 USINT

0…17

Table A.62

Attribute
ID

Access
Rule

Name

Data Type Min/Max

Default

Description