Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 96

Advertising
background image

5-37 Specifications

Publication 198-UM002A-EN-P December 2001

Assembly Instances 104 and 105 are default for 198-DNG. Assembly Instances 106 and 107
are default for 198-DN.

Input 1 represents the disconnect status of the distributed starter. Input 2 represents the contactor feedback

of the preset speed module. If this bit is set, the disconnect or contactor is closed. If this bit is not set, the
disconnect or contactor is open.

Figure 5.25 Cat. No. 198-IA2XOW1 Typical Wiring

Table 5.26 198-IA2XOW1 I/O Produced/Consumed Data

Input Data — Assembly Instance 103, 105, or 107

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Input 2

Input 1

Input Data — Assembly Instance 101

Bit 3 or 7

Bit 2 or 6

Bit 1 or 5

Bit 0 or 4

Input 2

Input 1

Output Data — Assembly Instance 102, 104, or 106

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Output 1

Output Data — Assembly Instance 100

Bit 3 or 7

Bit 2 or 6

Bit 1 or 5

Bit 0 or 4

Output 1

Typical Wiring for Series A

Typical Wiring for Series B

IN1
IN2
Out A
N

N
L

Input 1

Input 2

Output 1

Lout

120V AC

Out A

L

N

In1

In2

N

Advertising