Specifications 5-2

Publication 198-UM002A-EN-P December 2001

Table 5.1 Mod/Net Status LED

For this state:

MS/NS LED is:

To indicate:

Powerup and Autobaud

Flashes
green-red-off

When power is connected, the LED will flash this
pattern one time.
When waiting to detect the baud rate, the LED will flash
this pattern about every 3 seconds.

Not Powered/Not On-Line
Device is not on-line

Off

The device has not completed the Dup_MAC_ID test
yet.
The device may not be powered.

Device Operational and
On-line, Connected

Green

The device is operating in a normal condition and the
device is on-line with connections in the established
state.

Device Operational and
On-line, Not Connected or
Device On-line and needs
commissioning

Flashing Green

The device is operating in a normal condition and the
device is on-line with no connections in the established
state. The device has passed the Dup_MAC_ID test, is
on-line, but has no established connections to other
nodes.

Minor Fault and/or
Connection Time-Out

Flashing Red

Recoverable fault and/or one or more I/O Connections
are in the Timed-Out state.

Critical Fault or Critical Link
Failure

Red

The device has an unrecoverable fault; may need
replacing. Failed communication device. The device has
detected an error that has rendered it incapable of
communicating on the network (Duplicate MAC ID, or
Bus-off).

Communication Faulted and
Received an Identify Comm
Fault Request — Long
Protocol

Flashing Red and
Green

A specific Communication Faulted device. The device
has detected a Network Access error and is in the
Communication Faulted state. The device has
subsequently received and accepted an Identify
Communication Faulted Request — Long Protocol
message.