Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 69

Advertising
background image

Specifications 5-10

Publication 198-UM002A-EN-P December 2001

These specifications are for reference only. Refer to sensor specification for exact values.

Module Voltage Rating

24V DC

Module Operating Voltage Range

11…25V DC

Module Current Draw w/o Sensor

26 mA @ 24V DC

Input Voltage Rating

24V DC

Input On-State Voltage

10…26V DC

Input On-State Current

3.0 mA @ 10V DC
7.2 mA @ 24V DC

Input Off-State Voltage

0…5V DC

Input Off-State Current

< 1.5 mA

Short Circuit Detect Level

< 2V DC

Open Circuit Detect Level

< 100

µ

A

Module Isolation

Non-isolated mis-wire protected

Input Filter — Software
Selectable (with two I/O modules)

Off to On

1, 2, 4, 8, 16 ms

On to Off

1.3, 2, 4, 8, 16 ms

Input Compatibility

IEC 1+

Sensor

Sensor Operating Voltage

Typ. 3-wire

11…25V DC

Typ. 2-wire

18…25V DC

Sensor Current Draw Max.

100 mA

Environmental

Ambient Temperature

Operating

–25…+40°C (–4…+104°F)

Storage

–40…+85°C (–40…+185°F)

Relative Humidity

0…95% non-condensing

Shock

Operating

30 g peak acceleration

Non-Operating

50 g peak acceleration

Operating Vibration

10 g @ 58…2000 Hz
0.060 in. peak-to-peak displacement 2…57 Hz
Per IEC 68-2-6

Approvals

Agency Certification
(when product is marked)

cULus Listed
CE marked for all applicable directives

Table 5.7 198-IB2S Specifications (Continued)

Advertising