Nibble-wise input (produced) assemblies, Instance 101, Custom parameter based “word-wise” i/o assemblies – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 153

Advertising
background image

DeviceNet Information A-19

Publication 198-UM002A-EN-P December 2001

Nibble-wise Input (Produced) Assemblies

Instance 101

This input (produced) assembly was included in the Series B MDSA. Its length (in bytes) can
be calculated as follows:

(I/O module + 1 + (no. of IB2XOB2S modules) / 2) + 5

Unlike the “Byte-wise” output assemblies whose “location” bits operate as a binary location
count, the above “Nibble-wise” assembly contains a single location bit for each possible
module. The error location is simply given by setting the corresponding bit, rather than
generating a binary coded module number.

Custom Parameter Based “Word-wise” I/O Assemblies

The contents of these assemblies are determined by contents of the “Assembly Word X”
parameters in the EDS files.

Table A.28 Instance 100 — Nibble-wise Output Assembly Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Module 2 data

Module 2 data

1

Module 4 data

Module 4 data

:

:

:

:

:

:

N/2

Table A.29 Instance 101 — Nibble-wise Input Assembly Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Status 8

Status 7

Status 6

Status 5

Status 4

Status 3

Status 2

Status 1

1

Status 16

Status 15

Status 14

Status 13

Status 12

Status 11

Status 10

Status 9

2

Location 8

Location 7

Location 6

Location 5

Location 4

Location 3

Location 2

Location 1

3

Location 16 Location 15 Location 14 Location 13 Location 12 Location 11 Location 10 Location 9

4

Error code

5

Module 2 data

Module 1 data

6

Module 4 data

Module 3 data

:

:

:

:

:

:

(N+5)/2