Reversing distributed starter i/o assemblies – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual

Page 172

Advertising
background image

B-4 Motor Starter Operation

Publication 198-UM002A-EN-P December 2001

Instance 150 is the default output (consumed) assembly for Standard Distributed Starters

Standard Distributed Starter Input (Produced) Assemblies

Instance 52 is the required input (produced) assembly defined in the DeviceNet Motor Starter
Profile.
Instance 151 is the default input (produced) assembly for Standard Distributed Starters

Reversing Distributed Starter I/O Assemblies

These assemblies are available when the Motor Starter Type parameter is set to the value 2 =
Reversing Starter.

Reversing Distributed Starter Output (Consumed) Assemblies

Instance 3 is the required output (consumed) assembly defined in the DeviceNet Motor
Starter Profile.

Instance 152 is the default output (consumed) assembly for Standard Distributed Starters

Reversing Distributed Starter Input (Produced) Assemblies

Instance 52 is the required input (produced) assembly defined in the DeviceNet Motor Starter
Profile.

Instance 153 is the default input (produced) assembly for Reversing Distributed Starters

Table B.2 Instance 150 — Default Consumed Standard Distributed Starter

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Output 8

Output 7

Output 6

Output 5

Output 4

Output 3

Output 2

Run

1

Output 16

Output 15

Output 14

Output 13

Output 12

Output 11

Output 10

Output 9

Table B.3 Instance 151 — Default Produced Standard Distributed Starter

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Location 1 Location 0 Status 6

Status 5

Status 4

Status 3

Status 2

Status 1

1

Error 6

Error 5

Error 4

Error 3

Error 2

Error 1

Error 0

Location 2

2

Input 8

Input 7

Input 6

Input 5

Input 4

Input 3

Input 2

Input 1

3

Input 16

Input 15

Input 14

Input 13

Input 12

Input 11

Input 10

Input 9

4

Input 24

Input 23

Input 22

Input 21

Input 20

Input 19

Input 18

Input 17

Table B.4 Instance 152 — Default Consumed Reversing Distributed Starter

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Output 8

Output 7

Output 6

Output 5

Output 4

Output 3

Run Rev

Run Fwd

1

Output 16

Output 15

Output 14

Output 13

Output 12

Output 11

Output 10

Output 9