Motor Starter Operation B-5

Publication 198-UM002A-EN-P December 2001

Inverter Type Distributed Starter I/O Assemblies

These assemblies are available when the Motor Starter Type parameter is set to the value 3 =
Inverter Starter.

Inverter Type Distributed Starter Output (Consumed) Assemblies

Instance 3 is the required output (consumed) assembly defined in the DeviceNet Motor
Starter Profile.
Instance 154 is the default output (consumed) assembly for Inverter Type Distributed Starters

Inverter Type Distributed Starter Input (Produced) Assemblies

Instance 52 is the required input (produced) assembly defined in the DeviceNet Motor Starter
Profile.
Instance 155 is the default input (produced) assembly for Inverter Type Distributed Starters

Distributed Starter Specific DeviceNet Objects

When a Cat. No. 198-DNG is programmed to present itself as a Distributed Starter on
DeviceNet, two start-specific objects become visible via DeviceNet. These two objects are

Table B.5 Instance 153 — Default Produced Reversing Distributed Starter

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Location 1 Location 0 Status 6

Status 5

Status 4

Status 3

Status 2

Status 1

1

Error 6

Error 5

Error 4

Error 3

Error 2

Error 1

Error 0

Location 2

2

Input 8

Input 7

Input 6

Input 5

Input 4

Input 3

Input 2

Input 1

3

Input 16

Input 15

Input 14

Input 13

Input 12

Input 11

Input 10

Input 9

4

Input 24

Input 23

Input 22

Input 21

Input 20

Input 19

Input 18

Input 17

Table B.6 Instance 154 — Default Consumed Inverter Type Distributed Starter

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Output 8

Output 7

Output 6

Preset 2

Preset 1

Preset 0

Run Rev

Run Fwd

1

Output 16

Output 15

Output 14

Output 13

Output 12

Output 11

Output 10

Output 9

Table B.7 Instance 155 — Default Produced Inverter Type Distributed Starter

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Location 1 Location 0 Status 6

Status 5

Status 4

Status 3

Status 2

Status 1

1

Error 6

Error 5

Error 4

Error 3

Error 2

Error 1

Error 0

Location 2

2

Input 8

Input 7

Input 6

Input 5

Input 4

Input 3

Input 2

Input 1

3

Input 16

Input 15

Input 14

Input 13

Input 12

Input 11

Input 10

Input 9

4

Input 24

Input 23

Input 22

Input 21

Input 20

Input 19

Input 18

Input 17