3-32 Operator

Interface

7000A-RM001A-EN-P – January 2011

7000 “A” Frame


Drive Setup

This section describes how to:

select an alternate language

enter data to a drive parameter

assign a tag to an analog port

enable and disable a fault via a mask

assign text to be associated with optional external fault inputs

re-enter Setup Wizard

configure the XIO link

define the tags to be accessible by a PLC.


You will access the "SETUP" screen from the Top Level Menu by
pressing the [F8] key. This will result in the typical screen shown in
Figure 3.39 .


The Current Access level is shown. If it states 'Monitor' then you are
restricted to only viewing the basic drive setup. You cannot make
any changes. You must be in at least the 'Basic' access level in order
to modify any of the drive parameters, and you may only modify the
parameters for which you can view at the given access level.


At power-up, the operator interface access level is 'Monitor'. If this
is the current mode and you wish to change any of the setup data,
press the [F8] key now in order to change the access level before
proceeding into any of the other setup operations available from this
screen (Figure 3.40). Refer to the section Enter/Modify an Access
Level .

Figure 3.39 – Setup Screen