Commissioning 4-87
7000 “A” Frame
7000A-RM001A-EN-P – January 2011
While performing a live synchronous transfer:
• Capture motor voltage at ACB test point “Vuv” & bypass
voltage at ACB test point “Vuvs”.
• Capture and trigger on falling edge of the DC Link current
waveform at ACB test point “Idc1”.
• Label the waveforms as “Vuv”, “Vuvs” and “Idc1”.
• Save the worksheet as “Synch on Motor 01”, for example.
Table 4.J – Oscilloscope Setting
Oscilloscope
Time Base
Waveform
Test-Point
Waveform
Label
Ch. 1
DC Link Current
Idc1
Idc1
Ch. 2
Motor Voltage
Vuv
Vuv
Ch. 3
10ms/div.
Bypass Line
Voltage
Vuvs Vuvs
Live Synchronous Transfer Capture (50Hz System)
Ch1:
Idc1 (black), Ch2: Vuv (red), Ch3: Vuvs (blue)