Component Definition and Maintenance 5-117
7000 “A” Frame
7000A-RM001A-EN-P – January 2011
14.
Press F5 [POST] key and enter 10 (this is the percentage of post-
trigger samples) and then press the Enter key.
15.
Now, press F10 [EXIT] key to exit to ‘Diagnostic’ screen. On the
‘Diagnostics’ screen, verify that the Status is ‘Running”, which means
the Diagnostic Trend is ready and will capture the data whenever the
trigger condition is satisfied. If the Status shows ‘Stopped’ then press
F7 [Re-Arm] key. This will change the Status to Running.
16.
Now press F10 [EXIT] to exit to the main screen.