5-104

Component Definition and Maintenance

7000A-RM001A-EN-P – January 2011

7000 “A” Frame


PF7000 in Download Mode

To place the drive in download mode, you should be in the UTILITY –
TRANSFER screen. You will not be able to do this if the drive is
running. Ensure the drive is stopped, and the E-Stop is pressed. This is
just a precaution, as all versions of firmware 7.xxx and later will not allow
you to attempt a download while running.


This time press F9 for SYSTEM, and a screen will appear telling you that
you are in download mode, and to recycle control power once the
download is complete.

There are two status LEDs (D9 and D11) on the DPM, which provides
indication of the programming process. The following illustrates the
states of the LED:

Solid

Green – when both LEDs are solid green, the Application

firmware is running.

Flashing Green – when either D9 or both LEDs are flashing, the
board is in download mode. (If the DPM bootcode is ≥ 1.005, then
only D9 will be flashing and D11 will stay solid. But if the bootcode
is ≤ 1.005, then both LEDs will be flashing.)

After putting the drive in download mode, the following is the display on
the drive terminal:


SYSTEM IS IN DOWNLOAD MODE

Connect your PC to DPM data port

And download new firmware.

Press any Key to Continue …

Preparation for
Downloading Firmware
(cont.)

Advertising