Control power tests, Three-phase input – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 189

Advertising
background image


Commissioning 4-35

7000 “A” Frame

7000A-RM001A-EN-P – January 2011


Control Power Tests

I M P O R T A N T

I M P O R T A N T

Prior to energizing the drive, verify that the
control power being fed into the input breakers
is rated as designated on the electrical diagram.


Although there are a variety of options available to customers
that will effect the control power distribution within the drive,
the input will always be as illustrated below:


20V

ISOLATED

GATE DRIVER

POWER SUPPLY

Single Phase

AC/DC

Converter

56V

1000W or

1500W

+5V-LOGIC

+/-15V-LOGIC

+/-24V-HECS

+24V-ISOLATORS

+24V-XIO

20V

DC/DC

CONVERTER

Fan

SENSE
CABLE

DC Fail

120V

Single

phase

Grounded

Neutral

CB1

Customer

supplied

3-ph

C hold-up

CPT1

Optional

1-ph

&

Remote

I/O

PV550

Figure 4.8 – Control Power Distribution


Three-Phase

Input


In the 3-phase input configuration, the customer supplies 3-phase
control power into the Disconnect Switch (Labeled DS1 on the
Electrical Schematics). From that point, the power is distributed to
the 3-phase fan and to the power supplies through a single phase
CPT. The output of the single phase CPT powers all the power
supplies and controls within the drive. The 3-phase control should be
measured at the input to DS1. If the rating matches the designation
on the electrical schematic, it is acceptable to apply control power to
the drive. Take necessary measures to rectify the control power level
in the event that it does not meet the design specifications.