4-78 Commissioning

7000A-RM001A-EN-P – January 2011

7000 “A” Frame


Capturing Data

When all of the final commissioning procedures are completed and
the drive is running, it is VERY IMPORTANT TO CAPTURE ALL
THE DRIVE DATA for future reference.


The last step should be to PRINT DRIVE SETUP. This will print
all the parameters (regardless of the user access level), the various
firmware revisions, the exploded fault masks, the PLC links, and the
Analog configuration.


All of this information is required to address future customer issues.



GUIDELINES FOR DATA CAPTURE

This section provides some guidelines for capturing required
commissioning data and setting up oscilloscope to capture the
waveforms. For detailed instructions, always refer to
PowerFlex7000 user manual. Some sample waveforms have been
included for reference purpose.

After applying medium voltage to the drive, perform an input voltage
phasing check.

Summary:

• Drive input contactor should be closed. If the drive input contactor

configuration is set to NOT RUNNING, you will have to
temporarily change it to ALL FAULTS.

• Ensure that the drive is not running when capturing these

waveforms.

• Capture the three line voltage waveforms at ACB test points

– Master

winding: V2uv, V2vw & V2wu

• Label the waveforms as “V2uv”, “V2vw” and “V2wu”, etc.
• Save the worksheet as “Input Phasing”.

Drive Input Voltage
Phasing Checks