Commissioning 4-53

7000 “A” Frame

7000A-RM001A-EN-P – January 2011


Use the down arrow to highlight the output
you wish to assign. When you press Enter,
you will be brought to the entire list of
parameters in the Select Group screen. Use
the arrow and enter keys to find the parameter
you wish to assign, and press Enter. This will
take you back to the Analog screen and you
will see the new parameter name beside your
selected output.

Press EXIT [F10], go up to Parameters. Press
Enter, and then scroll down the list until you
reach Analog Outputs. Press Enter, and you
will see the same list of available ports and
the assigned parameter number, but not the
name.


If you scroll down, you will reach the scaling
factors for the 4 Meter Port and the 3 ACB
Port outputs. All parameters are scaled to 0-
10V, with 0 representing the minimum value
given in Chapter 5 under Parameter
Descriptions, and 10V representing the
maximum value given in Chapter 5. These
Scaling parameters (i.e. Anlg Port2 Scle) can
be used to change the scaling.

Note: There are certain parameters whose minimum value is a negative number. In that

case, the minimum value of the parameter (-10V) is scaled to 0V output, and the
maximum value is scaled to 10V output.