Installation of neutral resistor assembly – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 44

Advertising
background image

2-14

Drive Installation

7000A-RM001A-EN-P – January 2011

7000 “A” Frame

Assembled Acoustic

Exhaust Hood

Hood Ground Stud

M6 Screw.

Remove existing screw
and reinsert with Hood.

(Quantity = 11)

M6 Screw

(Quantity = 6)

Ground Exhaust Hood here.

(Use Green M6 Screw)

Neutral Resistor Assembly

Top Plate for Converter
and Common Mode
Choke/DC Link Cabinet


Figure 2.10 – Acoustic Hood Assembly for Neutral Resistor


Installation of Neutral Resistor Assembly

(Drives with Common Mode Chokes)

On top of the converter cabinet, a sheet metal enclosure containing
power resistors is to be installed.

1. Locate the resistor assembly on top of the cabinet as shown in

Figure 2.9. (For acoustic hood assembly, refer to Figure 2.10.)

2. Affix the assembly to the top plate using M6 thread forming

screws provided.

3. Remove the top plate of the resistor assembly to permit access to

the wiring connection points.

4. Connect the resistor wiring and per the electrical diagram

provided with the drive, a typical connection diagram is shown
in Figure 2.9. Ensure that the resistor wiring is routed through
the hole having a plastic bushing to protect the wire insulation.
The neutral resistor assembly housing has a ground connection
that is to be connected to the top plate of the drive.

5. Re-install the top plate of the neutral resistor housing.

Advertising