Replacement procedure for dc/dc power supply – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 314

Advertising
background image



5-72

Component Definition and Maintenance

7000A-RM001A-EN-P – January 2011

7000 “A” Frame


Terminal/connections descriptions (cont.)


P3 – ISOLATOR
(To Isolator Modules)

PIN NO.

LABEL

DESCRIPTION ONLY

1

ISOLATOR

(+24V,1A)

+24V,1A/com4

2

ISOL_COMM

(com4)

0V/com4

3

EARTH EARTH

P4 – PWR
(To ACB)

PIN NO.

LABEL

DESCRIPTION ONLY

1

+24V_XIO

(+24V,2A)

+24V,2A/com3

2

XIO_COMM

(com3)

0V/com3

3

+HECSPWR

(+24V,1A)

+24V,1A/com2

4

LCOMM

(com2)

0V/com2

5

–HECSPWR

(-24V,1A)

-24V,1A/com2

6

+15V_PWR

(+15V,1A)

+15V,1A/com1

7

ACOMM

(com1)

0V/com1

8

–15V_PWR

(-15V,1A)

-15V,1A/com1

9

+5V_PWR

(+5V,5A)

+5V,10A/com1

10

DGND

(com1)

0V/com1

11

EARTH earth

ground


Replacement Procedure for DC/DC Power Supply

(Refer to Figure 5.57)

1. With the drive energized, check that all output voltages are present.

(View 1)

2. De-energize the drive, isolate and lock out the control power, and

remove all wire connections from the unit. (View 1)

3. Remove quantity of (4) M6 (H.H.T.R.S.) that will allow the DC/DC

Power Supply Assembly to be removed from the Low Voltage Panel.
(View 1)

4. Remove quantity of (4) M4 (P.H.M.S.) and Nylon Shoulder

Washers from the back of the Mounting Plate. ( View 2)

5. Replace old DC/DC Power Supply with the new one.

NOTE: Make sure the Black Insulation is between the DC/DC
Power Supply and the Mounting Plate. Repeat Steps 4, 3, 2, 1
in this order to replace unit. (View 2)

6. Ensure the ground wire of P4 plug is connected to the ground by M10

bolt

DC/DC Power Supply
(cont.)