Component Definition and Maintenance 5-59

7000 “A” Frame

7000A-RM001A-EN-P – January 2011

Control Power Components

There are two configurations in which control power will be distributed
for the drive. The different methods are dependent on what drive option
the customer has chosen:

1.

AFE Rectifier with DTD DC Link – Conf. #1 (refer to Figure 5.44)

2.

AFE Rectifier with Separate Isolation Transformer – Config. #2

(refer to Figure 5.45)

3.

AFE Rectifier with Integral Isolation Transformer – Config. #3

(refer to Figure 5.45)

Ride-Through


Standard controls with 5 cycle ride-through – The drive main control
boards will remain energized for a total of 5 cycles after control power is
interrupted. If control power is not restored during the 5 cycles, a
controlled shutdown will occur.


Figure 5.44 illustrates the control power distribution for AFE drives with
integral starter/line reactor.

Printer

Operator Interface

Relays

DC/DC CONVERTER

VFD

AC/DC Converter

56V DC

1000W/1500W

+5V-LOGIC

+/-15V-LOGIC

+/-24V-HECS

+24V-ISOLATORS

+24-XIO

SENSE CABLE

20V

C Hold-up

Fan

20V Isolated

Gate Driver

Power Supply

380V 50Hz

or

460V 60Hz

3-ph

DC Fail

Fuse

Line

Reactance

120V

1-ph

Figure 5.44 – AFE Rectifier with DTD DC Link (Configuration #1)