Commissioning 4-63

7000 “A” Frame

7000A-RM001A-EN-P – January 2011

3.

Set

parameter

Idc Test Command in Current Control to 0.225 pu

for AFE rectifier drives and 0.400pu for SCR drives.


4.

Set

parameter

CurReg Bandwidth in Current Control to 100

rad/sec. A lower than the normal bandwidth makes the step
response easier to measure.


5.

Set

parameter

T DC Link in Current Control to 0.020 sec, which

is at the low end of the normal range of values and should
produce an under-damped response.

6.

Assign

parameters

Idc Reference and Idc Feedback in the

Current Control group to 2 DPM test points e.g. RTP1 and
RTP2. This can be done similarly to the way that the meter
assignments were described earlier in the chapter. Then they can
be displayed on the oscilloscope.

7. Start the drive. Set parameter Idc Ref Step in Current Control to

0.075pu for AFE rectifier drive and 0.200 pu for SCR drives.
The dc link current will step up and down by this amount at
regular intervals.


9. Adjust the scope to trigger on the rising edge of the dc current

reference and observe the dc current feedback on the other
channel. The step response will probably have noticeable
overshoot, indicating that the dc link time constant is set too low.


10.

Adjust

parameter

T DC Link until the current feedback rises to

about 63% of its final value in 10 ms as shown in the figure. The
overshoot should now be quite small. Increasing T DC Link
causes the rise time to increase. Since the desired step response
is slightly under-damped, T DC Link should not be increased
beyond the value at which the overshoot disappears.

Idc Reference

Idc Feedback

63%

0%

Figure 4.17 – Current Regulator Tuned Incorrectly