Sharing resistors, Testing sharing resistors, Snubber and sharing resistor replacement (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual
Page 274

5-32
Component Definition and Maintenance
7000A-RM001A-EN-P – January 2011
7000 “A” Frame
Push Nut
Resistor Bank
Retaining Rod
Figure 5.25 – Removing resistor bank from PowerCage
5. Remove the resistor bank from the Power Cage.
6. Place the new resistor bank assembly back into the PowerCage.
7. Slide the retaining rod into place and push the clips back into place.
8. Connect the leads to the resistor bank
9. Install the PowerCage as outlined in “PowerCage Removal”.
Sharing Resistors
Sharing resistors provide equal sharing of the voltage when matched
devices are used in series. SGCT PowerCages for 2400V systems do not
need matched devices and have no sharing resistor.
Testing Sharing Resistors
It is possible to verify the resistance value of the sharing resistors without
removing the PowerCage from the cabinet. Follow the procedures in
Chapter 4 – Commissioning.
Snubber and Sharing
Resistor Replacement
(cont.)