Commissioning 4-29

7000 “A” Frame

7000A-RM001A-EN-P – January 2011


Adjust deadbolt counterpart
so that grease marks from
pins hit here.

Grease marks

from deadbolt pins

Figure 4.1 – Deadbolt Assembly Mounted to Door


1. Lock out and isolate the drive from medium voltage. Verify with

a hot stick that there is no medium voltage present.


2. Determine that the key interlock is correctly aligned by securely

bolting the medium voltage doors of the cabinet closed and
removing the key from the lock. The key should turn easily; if
any force is required to turn the key, the deadbolt alignment
requires adjustment.


3.

Open the doors of the cabinet and inspect the key assembly.

Place high visibility grease on the pins of the deadbolt
counterpart. The factory recommends using yellow torque
sealant, however if it is unavailable almost any grease will do.
(See Figure 4.

1

)

Place grease on

deadbolt pins here.

Figure 4.2 – Deadbolt Counterpart Mounted to Cabinet