Operator Interface 3-59

7000 “A” Frame

7000A-RM001A-EN-P – January 2011


Once the data has started to be collected, the status will show
'triggered' as in Figure 3.84. When the buffer contains a complete
capture, it will show “stopped” (if a single capture), as shown in
Figure 3.85. The time and date at which the trigger occurred is
displayed. The trend buffers may only be viewed when their status is
‘stopped’. If in continuous mode, the capture will stop when the
buffers are viewed. To view the trend buffers, press the [F9] key.


Figure 3.85 – Diagnostic Stopped

Figure 3.86 – View the Trend Buffer(s)

A screen such as Figure 3.86 will be shown. Upon initial entry, the
screen will be positioned to the trigger point, shown by the "T ->". To
view data either side of the trigger point, press the [F8] and [F9] keys.


Changes made to the diagnostic list setup are not permanent unless
they are saved to the NVRAM in the drive. Upon exiting the
DIAGNOSTICS screen (Figure 3.79), you will be prompted to save
the changes to NVRAM. Refer to the section "Message Prompting"
for further details.