Drive processor module (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 318

Advertising
background image



5-76

Component Definition and Maintenance

7000A-RM001A-EN-P – January 2011

7000 “A” Frame

The following is the list of test points on the DPM:

Table 5.B – Test Points on Drive Processor Module

Test points

Name

Description

DPM-TP1

+1.2V

+1.2V DC power supply

DPM-TP2

+1.8V

+1.8V DC power supply

DPM-TP3

+2.5V

+2.5V DC power supply

DPM-TP4

+3.3V

+3.3V DC power supply

DPM-TP5

+5V

+5V DC power supply

DPM-TP6 DGND

Digital

ground

DPM-TP8

ITP1

Digital to Analog output – Assignable diagnostic test point

DPM-TP9

ITP2

Digital to Analog output – Assignable diagnostic test point

DPM-TP10

ITP3

Digital to Analog output – Assignable diagnostic test point

DPM-TP7

ITP4

Digital to Analog output – Assignable diagnostic test point

DPM-TP11

RTP4

Digital to Analog output – Assignable diagnostic test point

DPM-TP12

RTP3

Digital to Analog output – Assignable diagnostic test point

DPM-TP13

RTP2

Digital to Analog output – Assignable diagnostic test point

DPM-TP14

RTP1

Digital to Analog output – Assignable diagnostic test point

This table defines the states of LEDs D9 and D11 on the DPM board. D9
is used for the Inverter side processor and D11 is for the Rectifier side
processor. The other two LEDs (D6 and D7) are the watchdogs for the
Inverter and Rectifier code respectively.

Table 5.C – Description of D9 and D11 Function

Color

Rate or Count (Pulse)

Meaning

Green

10 Count

PreExecution OK

Red

.25 Hz

No Bootcode

Green

.25 Hz

No Application

Green

.5 Hz

Downloading via Serial Port

Green

2 Hz

Serial Port Active – i.e. Terminal

Green

1 Hz

Waiting/Loading Application

Green

Solid

Operation Running or Successful

Red Solid

Operation

Failed

Red

2 Count

POST – RAM Failed

Red

3 Count

POST – NVRAM Failed

Red

4 Count

POST – DPRAM Failed

Red

8 Count

FPGA Loading Failed

Red 9

Count

POST – USART Failed:
1 Green Count = Port 1
2 Green Count = Port 2

Red

10 Count

End of Code Reached

Red

11 Count

Download – CRC Error

Red

14 Count

Download – Overflow Error


Drive Processor Module
(cont.)

Advertising