Commissioning 4-69

7000 “A” Frame

7000A-RM001A-EN-P – January 2011


Tuning

abort - indicates that the deviation in motor speed was

greater than 10 Hz. The measured inertia value is invalid.
Parameter Autotune Trq Stp must be set to a lower value and the
test repeated.

Inertia

high - indicates that the measured total inertia is greater

than 20 seconds. This warning is intended to draw attention to
an unusually high inertia value. For a very high inertia load such
as a large fan, this may be a valid result and parameter Total
Inertia should be manually set equal to Autotune Inertia.
However, a high inertia measurement could also be produced by
a value of Autotune Trq Stp which is too low.



Flux Regulator Manual Tuning [Induction Motor]

1. Adjust the reference command to a value between 20 and 30 Hz.

2. Start the drive and wait for it to accelerate to the commanded speed.

3. Record the value of parameter Lm Measured (134) in Motor

Model.

4. Stop the drive.

5.

Set

parameter

Lm Rated in Motor Model to the recorded value of

Lm Measured.

6. Calculate an approximate value of the rotor time constant using

the following formula:

Slip

Rated

LmRated

T

rotor

=

Where

RPM

Sync

RPM

Rated

RPM

Sync

Freqmotor

Slip

Rated

)

(

)

2

(

×

= π

Set the parameter T Rotor in Motor Model to the calculated value.