Preventative Maintenance Schedule

D-9

7000 “A” Frame

7000A-RM001A-EN-P – January 2011




Rockwell Automation PowerFlex 7000 Preventative Maintenance Service Schedule

Interval

Period

(in

years)

0 1 2 3 4 5 6 7 8 9 10

Commissioning Activities

S

Door Mounted Air Filters

C/R C/R C/R C/R C/R C/R C/R C/R C/R C/R C/R

Main

Cooling

Fan

Motor

I I I I I I

RFB/R

I I I

Redundant

Cooling

Fan

Motor

(if

supplied) I I I I I I

RFB/R

I I I

Air-Cooling

System

Small Aux. Cooling Fans “Caravel”

I

I

I

I

R

I

I

I

I

R

Mesh Filters

C C C C C C C C C C C

De-ionizing Filter Cartridge

R R R R R R R R R R R

All

Fittings/Connections/Hose

Clamps

I I I I I I I I I I

Redundant

Cooling

Pump

Motors/Pumps I I I I I I I I I I

Redundant

Cooling

Pump

Motor

Seals I I I I I I I I I R

Liquid-Cooling

System

Thermostatic

Valve

Element

I I I I I I R I I I

Power

Devices

(SGCTs/SCRs)

I I I I I I I I I I

Snubber

Resistors/Sharing

Resistors/HECS

I I I I I I I I I I

Rectifier Snubber Capacitors

I

I

I

I

I

I

I

I I Rv/R

Inverter

Snubber

Capacitors

I I I I I I I I I R

Power Switching

Components

Integrated Gate Driver Power Supply

I

I

I

I

RFB/R

I

I

I

I

RFB/R

Isolation

Transformer/Line

Reactor

I I I I M I I I I M

DC Link/Common Mode Choke

I

I

I

I

M

I

I

I

I

M

Integral

Magnetics/Power

Filters

Line/Motor

Filter

Capacitors

I I I I M I I I I M

AC/DC and DC/DC Power Supplies

I

I

I

I

RFB/R

I

I

I

I

RFB/R

Control

Boards

I I I I I I I I I I

Batteries

(DCBs

and

CIB)

I I R I I R I I R I

Control Cabinet

Components

Batteries (UPS)

I I I I R I I I I R

Low Voltage Terminal Connections/
Plug-in Connections

I I I I I I I I I I

Medium

Voltage

Connections

I I I I I I I I I I

Heatsink

Bolted

Connections

I I I I I I I I I I

Medium Voltage Connections (Rectifier)

I

I

I

Connections

Medium Voltage Connections (Inverter)

– – – – – – – – – I

Firmware

– – Rv – – Rv – – Rv –

Enhancements

Hardware

– – Rv – – Rv – – Rv –

Parameters

I I Rv I I Rv I I Rv I

Variables

I I Rv I I Rv I I Rv I

Operational

Conditions

Application

Concerns

I I Rv I I Rv I I Rv I

Spare Parts

Inventory/Needs

I I Rv I I Rv I I Rv I

Only applies to air-cooled VFDs (i.e. ‘A’ Frame and ‘B’ Frame)

If filter supplied is not a washable type, replace filter. If filter supplied is a washable type, wash or replace (depending on state of filter).

Only applies to liquid-cooled VFDs (i.e. ‘C’ Frame)

A 4-year replacement interval applies to 6-pulse or 18-pulse versions. Active Front End rectifiers have a 10-year rectifier snubber capacitor replacement interval.

Replace UPS batteries yearly for 50°C rated VFDs.

When rectifier snubber capacitors are replaced, the MV connections for rectifier need to be inspected.

When inverter snubber capacitors are replaced, the MV connections for inverter need to be inspected.

These components may be serviced while the VFD is running.