Commissioning 4-49

7000 “A” Frame

7000A-RM001A-EN-P – January 2011



The PV550 display screens are given as an example. The actual
screen data may differ.

Ensure you have Advanced access.

Now, from the main screen, press
SETUP [F8] to get to Parameters,
and then Enter. You should be on
Feature Select, the first group.

Press Enter, Operating Mode is
highlighted on the first line.

Press Enter and use the down
arrow to get to System Test. Press
Enter, and then EXIT and you will
be in System Test mode. From
this point you can completely
check the entire system without
medium voltage. As long as you
have test power to all your
contactors, you can start, stop, E-
Stop, trigger faults, check remote
IO, check PLC inputs, and verify
other functionality.

A T T E N T I O N

A T T E N T I O N

Ensure that the drive is no longer running in
system test mode prior to applying medium
voltage to the drive line-up. Failure to do so
may result in equipment damage.