Table 5.E – Test Points on Analog Control Board (cont.)

Test points

Name

Description

ACB-TP51

CP1

Control Power monitoring for channel 1

ACB-TP52

CP2

Control Power monitoring for channel 2

ACB-TP53

CP3

Control Power monitoring for channel 3

ACB-TP54

CP4

Control Power monitoring for channel 4

ACB-TP55

Vltrp

AC Over Voltage Detection set point for 2UVW&3UVW

ACB-TP56 AGND

Analog

ground

ACB-TP57 AGND

Analog

ground

ACB-TP58 AGND

Analog

ground

ACB-TP59 AGND

Analog

ground

ACB-TP60

+5V

+5V DC power supply

ACB-TP61

+15V

+15V DC power supply

ACB-TP62

-15V

-15V DC power supply

ACB-TP63

+24V

+24V DC power supply

ACB-TP64

-24V

-24V DC power supply

ACB-TP65

24VCOM

+/- 24V common

ACB-TP66 DGND

Digital

ground

ACB-TP67 AGND

Analog

ground

ACB-TP68

AP1

Analog Control Inputs, Air pressure input, AP1

ACB-TP69

AP0

Analog Control Inputs, Air pressure input, AP0

ACB-TP70

AIN1

Analog Control Input ,AIN1

ACB-TP71

AIN2

Analog Control Input ,AIN2

ACB-TP72

AIN0

Analog Control Input ,AIN0

ACB-TP73

AIN3

Analog Control Input ,AIN3

ACB-TP74

IPIS

Input Isolating Switch

ACB-TP75

IPCS

Input Contactor Status

ACB-TP76

IP

Input Contactor Command

ACB-TP77

OPIS

Output Isolating Switch

ACB-TP78 OPCS

Output

Contactor

Status

ACB-TP79 OP

Output

Contactor

Command

ACB-TP80

BPIS

Bypass Isolating Switch

ACB-TP81 BPCS

Bypass

Contactor

Status

ACB-TP82 BP

Bypass

Contactor

Command

ACB-TP83

DGND

Digital Ground Return

ACB Analog Control
Board (cont.)