4-82 Commissioning

7000A-RM001A-EN-P – January 2011

7000 “A” Frame

DC Current Test

Perform DC Test. Refer to the commissioning section of the
PoweFlex7000 user manual for a more detailed procedure.

Summary:

• Make sure the Diagnostic Trend has been setup and is armed.

• Run the DC Test with Idc Command Test (P119) set to 0.1pu.

Increase Idc Command Test from 0.1

0.3pu (for AFE drives)

or from 0.1

0.7pu (for 18-pulse drives) in steps of 0.1pu. At

each step, verify DC link current regulation by monitoring Idc
Error (P323) and Alpha Line (P327).

• Capture DC link voltage waveform at ACB test point “Vdcr1”

and DC link current waveform at ACB test point “Idc1” at 0.3pu
(for AFE drives) or at 0.7pu (for 18-pulse drives).

• Label the waveforms as “Vdcr1”, and “Idc1”.

• Save the worksheet as “DC Test @ 0.3pu” (for AFE drives) or

“DC Test @ 0.7pu” (for 18-pulse drives).

Table 4.F – Oscilloscope Setting

Oscilloscope

Time
Base

Waveform

Test-

Point

Waveform

Label

Sheet
Name

Ch. 1

DC Link

Voltage

Vdcr1 Vdcr1

Ch. 2

2ms/div.

DC Link

Current

Idc1 Idc1

DC Test

Sample

Waveforms:

Sample waveforms of DC Test recorded on a AFE Drive

Idc Cmd Test = 0.2pu [Ch1- Vdcr1, Ch2 – Idc1 at ACB test points]