Specifications

Description

Specifications

Power Rating (Air Cooled)

200 to 1250 hp (150 to 933 kW)

Motor Type

Induction or Synchronous

Input Voltage Rating

2400V, 3300V, 4160V, 6600V

Input Voltage Tolerance

± 10% of Nominal

Voltage Sag -30%

Control Power Loss Ride-Through

5 Cycles (Std)

Input Protection

Surge Arrestors

Input Frequency

50/60 Hz, +/- 5%

Power Bus Short-circuit Current Withstand

5 Cycle

3300 V – 6000 V

25 kA RMS SYM

Basic Impulse Level

50 kV (0 – 1000 m)

Power Bus Design

Copper – Tin plated

Ground Bus

Copper – Tin plated 6 x 51 mm (¼ x 2 in.)

Customer Control Wire Way

Separate and Isolated

Input Power Circuit Protection

Vacuum Contactor with Fused Isolating Switch

(optional)

Input Impedance Device

Isolation Transformer or AC Line Reactor

Output Voltage

0 – 2300 V
0 – 3300 V
0 – 4000 V

0 – 6000 or 6300 V

Inverter Design

PWM

Inverter Switch

Symmetrical Gate Commutated Thyristor (SGCT)

Inverter Switch Failure Mode

Non-rupture, Non-arc

Inverter Switch Failure Rate (FIT)

100 per 1 Billion Hours Operation

Inverter Switch Cooling

Double Sided, Low Thermal Stress

Inverter Switching Frequency

420-540 Hz

Voltage

SGCTs (per phase)

Number of Inverter SGCTs

2400 V
3300 V
4160 V
6600 V

2
4
4
6

Voltage

PIV

SGCT PIV Rating
(Peak Inverse Voltage)

2400 V
3300 V
4160 V
6600 V

6500 V
6500 V
6500 V
6500 V

Rectifier Designs

AFE (Active Front End)

Rectifier Switch

SGCT

Rectifier Switch Failure Mode

Non-rupture, Non-arc

Rectifier Switch Failure Rate (FIT)

100 (SGCT) per 1 Billion Hours Operation

Rectifier Switch Cooling

Double Sided, Low Thermal Stress

Voltage Sag tolerance is reduced to -25% when control power is supplied from medium voltage via CPT.

Short-circuit fault rating based on input protection device (contactor or circuit breaker).

BIL rating based on altitudes < 1000 m (3,300 ft.) Refer to factory for derating on altitudes >1000 m).

Specifications