4-62 Commissioning

7000A-RM001A-EN-P – January 2011

7000 “A” Frame

7.

Record the value of the rectifier input voltage by looking at

parameter Rec Input Voltage (P696). Let this value be V

in1

.

8.

The value of input impedance for AFE drives is calculated as

follows:

drives

for

V

V

C

I

V

V

L

in

in

in

dc

in

in

in

PWM

)

(

1

0

1

0

+

=


C

in

is the value of input filter capacitor given by Line Filter Cap

(P133)

9.

The value of input impedance for SCR drives is calculated as

follows:

drives

SCR

for

I

V

V

L

dc

in

in

in

)

(

3

1

0

=


10.

Stop the drive. Set parameters Operating Mode to Normal and

Idc Command Test to zero.

T DC Link (P#115) Manual Tuning


An appropriate value for the T DC Link parameter can be determined
from the current regulator step response while operating in DC
Current test mode. The following procedure should be followed:


1. Be sure that all the parameters in the Drive Hardware and Motor

Ratings groups have been set to the correct values. Otherwise,
the calculated value of parameter T DC Link in Current Control
will not be correct.

2. Set

parameter

Operating Mode in the Feature Select to DC

Current to enter dc current test mode.

Current Control Parameter Screen

Tuning Procedure (cont.)