4-62 Commissioning
7000A-RM001A-EN-P – January 2011
7000 “A” Frame
7.
Record the value of the rectifier input voltage by looking at
parameter Rec Input Voltage (P696). Let this value be V
in1
.
8.
The value of input impedance for AFE drives is calculated as
follows:
drives
for
V
V
C
I
V
V
L
in
in
in
dc
in
in
in
PWM
)
(
1
0
1
0
⇒
−
+
−
=
C
in
is the value of input filter capacitor given by Line Filter Cap
(P133)
9.
The value of input impedance for SCR drives is calculated as
follows:
drives
SCR
for
I
V
V
L
dc
in
in
in
)
(
3
1
0
⇒
−
=
10.
Stop the drive. Set parameters Operating Mode to Normal and
Idc Command Test to zero.
T DC Link (P#115) Manual Tuning
An appropriate value for the T DC Link parameter can be determined
from the current regulator step response while operating in DC
Current test mode. The following procedure should be followed:
1. Be sure that all the parameters in the Drive Hardware and Motor
Ratings groups have been set to the correct values. Otherwise,
the calculated value of parameter T DC Link in Current Control
will not be correct.
2. Set
parameter
Operating Mode in the Feature Select to DC
Current to enter dc current test mode.
Current Control Parameter Screen