Motor impedance, Tuning procedure (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual
Page 218
 
 
4-64 Commissioning 
7000A-RM001A-EN-P – January 2011
7000 “A” Frame
Idc Reference
Idc Feedback
63%
0%
Figure 4.18 – Current Regulator Tuned Correctly
 
 
 11. 
Set
parameter
CurReg Bandwidth to the normal value of 200
rad/sec. Confirm that the rise time of the current feedback is 
now approximately 5 ms and that the overshoot is not excessive. 
 
 12. 
Set
parameter
Idc Ref Step to zero. The dc link current will
return to a steady level given by Idc Test Command.
 
 
13. Stop the drive. Set parameters Operating Mode to Normal, and
Idc Test Command to 0.000pu.
2. Motor Impedance
 
 
The motor impedance tuning function calculates stator resistance R 
Stator (129) and total leakage inductance L Total Leakage (130) in 
Motor model Group. These parameters are used in the reconstruction 
of the rotor flux. If these parameters are not adjusted correctly, the 
resulting distortion in the flux feedback may cause speed feedback or 
motor synchronization errors. These parameters must be tuned 
during commissioning because it is affected not only by motor 
parameters, but also by cable length. The tuning should be done with 
the motor stationary. 
A T T E N T I O N
A T T E N T I O N
In the following steps, the rotation of the motor in 
an undesirable direction may occur. To guard 
against possible equipment damage, it is 
recommended that the motor is disconnected from 
the load and tested for direction prior to 
proceeding, should the equipment be sensitive to 
reverse direction rotation. 
The following auto-tune procedure can be followed.
Tuning Procedure (cont.)