Cable insulation – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual
Page 60

2-30
Drive Installation
7000A-RM001A-EN-P – January 2011
7000 “A” Frame
Power Wiring Selection (cont.)
Cable Insulation
The cable insulation requirements for the PowerFlex 7000 “A”
Frame drive are given in the tables below.
A T T E N T I O N
A T T E N T I O N
Voltage ratings shown in the following
tables are peak line-to-ground. Some cable
manufacturers rate voltage line-to-line RMS.
Ensure the cable meets the rating specified
in the following tables.
Cable Insulation Requirements for AFE Drives with Separate Isolation Transformer
Cable Insulation Rating (kV)
(Maximum Peak Line-to-Ground)
System Voltage (V, RMS)
Machine Side
2400
≥ 4.1
≥ 2.2
3000
≥ 5.12
≥ 2.75
3300
≥ 5.63
≥ 3.0
4160
≥ 7.1
≥ 3.8
6000
≥ 10.8
≥ 5.5
6300
≥ 11.4
≥ 5.8
6600
≥ 11.8
≥ 6.0
Cabling from secondary side of Isolation Transformer to input of VFD
Cable Insulation Requirements for “Direct-to-Drive” Technology or Integral
Isolation Transformer
Cable Insulation Rating (kV)
(Maximum Peak Line-to-Ground)
System Voltage (V, RMS)
Line Side
Machine Side
2400
≥ 2.2
≥ 2.2
3000
≥ 2.75
≥ 2.75
3300
≥ 3.0
≥ 3.0
4160
≥ 3.8
≥ 3.8
6000
≥ 5.5
≥ 5.5
6300
≥ 5.8
≥ 5.8
6600
≥ 6.0
≥ 6.0