2-30

Drive Installation

7000A-RM001A-EN-P – January 2011

7000 “A” Frame

Power Wiring Selection (cont.)

Cable Insulation

The cable insulation requirements for the PowerFlex 7000 “A”
Frame drive are given in the tables below.

A T T E N T I O N

A T T E N T I O N

Voltage ratings shown in the following
tables are peak line-to-ground. Some cable
manufacturers rate voltage line-to-line RMS.
Ensure the cable meets the rating specified
in the following tables.

Cable Insulation Requirements for AFE Drives with Separate Isolation Transformer

Cable Insulation Rating (kV)

(Maximum Peak Line-to-Ground)

System Voltage (V, RMS)

Machine Side

2400

≥ 4.1

≥ 2.2

3000

≥ 5.12

≥ 2.75

3300

≥ 5.63

≥ 3.0

4160

≥ 7.1

≥ 3.8

6000

≥ 10.8

≥ 5.5

6300

≥ 11.4

≥ 5.8

6600

≥ 11.8

≥ 6.0

Cabling from secondary side of Isolation Transformer to input of VFD


Cable Insulation Requirements for “Direct-to-Drive” Technology or Integral
Isolation Transformer

Cable Insulation Rating (kV)

(Maximum Peak Line-to-Ground)

System Voltage (V, RMS)

Line Side

Machine Side

2400

≥ 2.2

≥ 2.2

3000

≥ 2.75

≥ 2.75

3300

≥ 3.0

≥ 3.0

4160

≥ 3.8

≥ 3.8

6000

≥ 5.5

≥ 5.5

6300

≥ 5.8

≥ 5.8

6600

≥ 6.0

≥ 6.0