Commissioning 4-85

7000 “A” Frame

7000A-RM001A-EN-P – January 2011

Synchronous Transfer

When commissioning a drive employing synchronous transfer, the
following waveforms should be captured and submitted with the
commissioning package. Refer to the “Synchronous Transfer
Commissioning Guidelines” for a detailed commissioning
procedure.

While measuring the bypass (BP) contactor closing time:

• Capture 120V bypass close command from the BP Contactor Close

output (J1-12) at the ACB (refer to electrical drawing for specific
wire/terminal number).

• Capture the 9V signal across the bypass contactor vacuum bottles

(refer to the tech note PF7000_GEN-78 for details).

• Label the waveforms as “BP_Close_Cmd” and “Actual_Closure”.

• Save the worksheet as “Bypass Contactor Close Delay”.

Table 4.H – Oscilloscope Setting

Oscilloscope Time Base

Waveform

Test-Point

Waveform Label

Ch. 1

BP Contactor

Close Command

BP Contactor

Close Cmd

BP_Close_Cmd

Ch. 2

25ms/div.

Actual Closure of

BP

Across 2K-Ohm

resistor

connected in

series with 9V

battery

Actual_Closure


Ch1: Bypass Contactor Close Command (BPC output at ACB, J1-12 & 402)

Ch2: Actual Closure of Bypass Contactor (using 9V battery across contactor
vacuum bottles)