Start/stop control circuit, Status indicators, System test (cont.) – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 204

Advertising
background image



4-50 Commissioning

7000A-RM001A-EN-P – January 2011

7000 “A” Frame

System Test (cont.)

Start/Stop Control Circuit


Once the drive is in System Test mode, ensure that the stop/start
circuit functions as desired. It may be necessary to study the
electrical schematic drawings, prior to performing this test, in order
to understand the control circuit.


Start the drive in local control while observing the system vacuum
contactors or customer supplied circuit breakers. If troubleshooting is
required in Rockwell Automation medium voltage switchgear,
additional information is available in the following publications:

Publication

1500-UM055_-EN-P, Medium Voltage Controller,

Bulletin 1512B, Two-High Cabinet, 400 Amp • User Manual

Publication

1503-IN050_-EN-P, OEM Starter Frame and

Components • Installation Manual

Publication

1502-UM050_-EN-P, Medium Voltage Contactor,

Bulletin 1502, 400 Amp (Series D) • User Manual

Publication

1502-UM052_-EN-P, Medium Voltage Contactor,

Bulletin 1502, 400 Amp (Series E) • User Manual

Publication

1502-UM051_-EN-P, Medium Voltage Contactor,

Bulletin 1502, 800 Amp • User Manual


If the Medium Voltage contactors or circuit breakers perform as
desired, stop the drive and perform the same test while operating in
remote control.


Start the drive again and verify that all emergency stops installed in
the system function as desired. Ensure that all electrical interlocks
installed in the system function as desired. Make any necessary
control wiring modifications at this time and re-test the system if
necessary.

Status

Indicators


Drive status is often feedback to a plant’s process control either
digitally through the PLC input/output feature (see Chapter 3 –
Operator Interface, PLC page 3-43) or through relay logic. The
following relays are provided with the drive as standard:

Relay Name

Relay Designation

Run Contact

Fault Contact

Warning Contact

Ready Contact

RUN

FLT

WRN

RDY

Advertising